Case: T07FR00479

Parcel: 13809007G


Addresses:

428 W VALENCIA RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00479

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2007 VIOL - BUILDING SVCS & SYSTEMS Approved All o.k. 4/3
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Electrical outlet plate covers missing.(2) (Check cash window, Produce office)
605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of the
code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used. 2003 IFC
**Replace outlet covers.
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Extension cords in use to power equipment.
*Motor room.(4)
*Bakery (3)
*Meat Dept. (2)
*Liquors (3)
605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
**Replace cord with UL approved power sources.
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Multiplug adapters in use. (Liquors)
605.4 Multiplug adapters. Multiplug adapters, such as cube
adapters, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited. 2003 IFC
**Replace with approved power strip.
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Open junction boxes in motor room.(numerous)
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes. 2003 IFC
**Repair ALL junction boxes.
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation -Electrical panels blocked.(Bakery, Motor room)
605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC
**Unblock ALL electrical panels.