Case: T07FR00479

Parcel: 13809007G


Addresses:

428 W VALENCIA RD


Inspection Status: Approved

Inspection History: VIOL - FIRE SERVICE FEATURES

Case Number - T07FR00479

Inspection Description - VIOL - FIRE SERVICE FEATURES

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2007 VIOL - FIRE SERVICE FEATURES Approved Sign installed 4/2
03/14/2007 VIOL - FIRE SERVICE FEATURES Violation -Riser room needs I.D. sign on door.
510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for airconditioning systems, sprinkler risers and valves, or other fire
detection, suppression or control elements shall be identified for
the use of the fire department. Approved signs required to identify
fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and
readily visible. 2003 IFC
**Install approved sign for riser room.