Case: T07FR00479

Parcel: 13809007G


Addresses:

428 W VALENCIA RD

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
04/05/2007 VIOL - PRECAUTION AGAINST FIRE Approved Abated 4/2
03/14/2007 VIOL - PRECAUTION AGAINST FIRE Violation -Combustible storage in motor room.
315.2.3 Equipment rooms. Combustible material shall not be
stored in boiler rooms, mechanical rooms or electrical equipment
rooms. 2003 IFC
**Remove all combustible storage in motor room.
03/14/2007 VIOL - PRECAUTION AGAINST FIRE Violation -Sprinkler head blocked.(Bakery)
315.2.1 Ceiling clearance. Storage shall be maintained 2 feet
(610 mm) or more below the ceiling in nonsprinklered areas of
buildings or a minimum of 18 inches (457 mm) below sprinkler
head deflectors in sprinklered areas of buildings. 2003 IFC
**Keep storage within limits.