Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | VIOL - PRECAUTION AGAINST FIRE | Approved | Abated 4/2 | |
| 03/14/2007 | VIOL - PRECAUTION AGAINST FIRE | Violation | -Combustible storage in motor room. 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 2003 IFC **Remove all combustible storage in motor room. |
|
| 03/14/2007 | VIOL - PRECAUTION AGAINST FIRE | Violation | -Sprinkler head blocked.(Bakery) 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 2003 IFC **Keep storage within limits. |