Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00476
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - MEANS OF EGRESS | Compliance | ALL O.K., EXCEPT ITEMS 13 AND 16. | |
03/14/2007 | VIOL - MEANS OF EGRESS | Violation | 12. Storage blocking path to exit door. (Stockroom) Corrected in my presence. 13. Clear path to public way blocked by fencing, storage.( Rear stockroom exit.) 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. 2003 IFC ***Unblock all exit pathways. |
|
03/14/2007 | VIOL - MEANS OF EGRESS | Violation | 14. 2 sets of panic hardware on exit door. (NW stockroom door) 1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code. 2003 IFC ***Remove one set of panic hardware, so that there is only one system on door. |
|
03/14/2007 | VIOL - MEANS OF EGRESS | Violation | 15. Exit door difficult to open, needs adjustment.(Tortilleria) 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). 2003 IFC ***Repair door. |
|
03/14/2007 | VIOL - MEANS OF EGRESS | Violation | 16. Directional exit sign neede to indicate exit. (Center Exit) 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. 2003 IFC ***Install directional Exit sign. |