Case: T07FR00476

Parcel: 137055220


Addresses:

1221 W IRVINGTON RD


Inspection Status: Compliance

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00476

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/02/2007 VIOL - FIRE PROTECTION SYSTEMS Compliance ALL O.K. 4/5
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 8. Fire extinguisher needs to be mounted. (Rear stockroom)
906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be se-
curely anchored to the mounting surface in accordance with the
manufacturer's installation instructions. 2003 IFC
***Mount extinguishers.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 9. Fire Department Connection (FDC) caps missing.
912.6 Inspection, testing and maintenance. All fire department
connections shall be periodically inspected, tested and
maintained in accordance with NFPA 25. 2003 IFC
***Replace FDC caps.
03/14/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 10. Storage rack blocking access to sprinkler riser.
11. Hood system pull station blocked. (Bakery)
508.5.4 Obstruction. Posts, fences, vehicles, growth, trash,
storage and other materials or objects shall not be placed or kept
near fire hydrants, fire department inlet connections or fire protection
system control valves in a manner that would prevent
such equipment or fire hydrants from being immediately discernible.
The fire department shall not be deterred or hindered
from gaining immediate access to fire protection equipment or
fire hydrants. 2003 IFC
***10. Clear space around riser by moving storage rack to create a clear passageway for fire personnel to access controls/valves.
***11. Remove storage from pull station area, so it is clearly visible.