Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00476
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | ALL O.K. 4/5 | |
03/14/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 3. Electrical panel blocked. (Pharmacy) Corrected in my presence. 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC ***Keep area in front of panels clear. |
|
03/14/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 4. Extension cord powering water softener system.(rear of store) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 2003 IFC ***Remove extension cords, replace with approved power source. |