Case: T07FR00476

Parcel: 137055220


Addresses:

1221 W IRVINGTON RD


Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00476

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
05/02/2007 VIOL - BUILDING SVCS & SYSTEMS Compliance ALL O.K. 4/5
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 3. Electrical panel blocked. (Pharmacy) Corrected in my presence.
605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. 2003 IFC
***Keep area in front of panels clear.
03/14/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 4. Extension cord powering water softener system.(rear of store)
605.5 Extension cords. Extension cords and flexible cords shall
not be a substitute for permanent wiring. Extension cords and
flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with portable
appliances. 2003 IFC
***Remove extension cords, replace with approved power source.