Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 03/13/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 605.1 REPAIR ELECTRICAL HAZARDS. 1) ELECTRICAL OUTLET IN BOOTH IN BLUE ROOM (SOUTH TV) 2) COVER PLATE NEEDED ON OUTLET BY RISER. |
|
| 03/13/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 605.4 USE APPROVED CUBE ADAPTERS. 1) REPLACE CUBE IN OFFICE WITH APPROVED ADAPTER. |
|
| 03/13/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 605.5 EXTENSION CORDS NOT ALLOWED. 1) REPLACE EXTENSION ON WATER HEATER WITH APPROVED POWER STRIP OR HARD WIRE IN. |
|
| 03/13/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 605.3 WORKING SPACE OF NOT LESS THAN 30 INCHES WID AND 36 INCHES IN DEPTH SHALL BE PROVIDED IN FRONT OF ELECTRICAL EQUIPMENT. 1) REMOVE STROAGE ITEMS AWAY FROM ELECTRICAL PANEL. |