Case: T07FR00463

Parcel: 13220007E

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/23/2007 INSP - FULL Violation Final inspection,no further action at this time.
03/09/2007 INSP - FULL Violation 2003 IFC-1008.1.8 The main exit door shall have the sign: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
2003 IFC-605.6 The wearhouse North wall electrical outlet damaged cover plate shall replace.
2003 IFC-1011.2 THe Wearhouse has two exit doors shall install the exit signs.
2003 IFC-605.6 Welding shop J-box damaged, shall replace cover plate.
2003 IFC-1008.1.8 Shop area exit door needs the exit sign.
2003 IFC-1008.1.8 The 2nd story exit doors needs two exit signs.
2003 IFC- 1011.2 exit illuminations are required in some of the exit doors. The ones with external illuminations do not need illumination from within.