Case: T07FR00440

Parcel: 12201024J


Addresses:

3920 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00440

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2007 VIOL - MEANS OF EGRESS Approved
03/06/2007 VIOL - MEANS OF EGRESS Violation Exit signs not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
_____Fix light in all exit signs.
03/06/2007 VIOL - MEANS OF EGRESS Violation Bar on door / Key lock:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
TFC 1027.6 [ammendment] Panic Hardware:
Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

_______Remove bar/ bolt and all associated hardware from back door.

______Remove key lock from Chase teller area, to assure egress for employees working in the area at all times.
03/06/2007 VIOL - MEANS OF EGRESS Violation Note: Make sure the panick hardware can be opened with 15 lbs of pressure, or less. Ask your service rep to assure they are compliant with the code. Thank you.