Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00440
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2007 | VIOL - MEANS OF EGRESS | Approved | ||
03/06/2007 | VIOL - MEANS OF EGRESS | Violation | Exit signs not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in all exit signs. |
|
03/06/2007 | VIOL - MEANS OF EGRESS | Violation | Bar on door / Key lock: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. TFC 1027.6 [ammendment] Panic Hardware: Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _______Remove bar/ bolt and all associated hardware from back door. ______Remove key lock from Chase teller area, to assure egress for employees working in the area at all times. |
|
03/06/2007 | VIOL - MEANS OF EGRESS | Violation | Note: Make sure the panick hardware can be opened with 15 lbs of pressure, or less. Ask your service rep to assure they are compliant with the code. Thank you. |