Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00440
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | Electrical violations abated. | |
03/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ______Replace with approved power strip. [in bakery]. ______Remove from passing through ceiling in all locations. [by managers office, by juice case] |
|
03/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. |
|
03/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Multiplug adapters: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices. |