Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST/UST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | INSP - AST/UST | Approved | Permenant bollards in place around oil tanks and natural gas piping.. Approved | |
| 03/14/2007 | INSP - AST/UST | Approved | Installed 2x 1000 gallon AST's, 1 new oil, 1 waste oil. Installed one 280 gallon antifreeze tank. All tanks are double wall steel. All have proper normal and emergency venting. Tanks located outdoors. Proper placards and lables are on the tanks. Approved Vehicle impact protection installed. New bollards on order to replace K rail. Will check for permenant bollards on 06-11-07 | |
| 03/06/2007 | INSP - AST/UST | Correction Required | New permit for 3 ASTs, 1 x 1000 gal new oil, 1x 1000 used oil, 1x 280 used anti-freeze. They need signage, no smoking, vehicle impact protection on north and south sides. Parts washers are not installed yet. Spray booths not complete. |