Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | INSP - REINSPECTION | Approved | approved | |
| 03/14/2007 | INSP - REINSPECTION | Violation | 1). A fire alarm test was required and the following still need to be repaired on fire alarm. Test dated 2-28-07 indicated the following repairs: A). "There is no supervisory wiring from main power supply to devices: B). "Bell is not supervised and has a switch to turn on and off that is not supervised" These corrections must be made as per NFPA 72 and IFC 901.6 |