Case: T07FR00417

Parcel: 12619188G


Addresses:

1101 S COLUMBUS BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/10/2007 INSP - FULL Approved approved
03/01/2007 INSP - FULL Violation 1). Certificate of Occupancy required. IBC 110
2). Lobby. Currently smoke alarm is hanging from ceiling by wires, repair smoke alarm. IFC 901.6
3). Trunk obstructing exit in kitchen. Relocate trunk from exit. IFC 1027.3
4). Currently clothes and coats are being stored in exit corridor
If classified as an E or I-4 daycare , all coats , clothes and personnel effects must be removed from lobby as per IFC which states:

803.3 Group E. The requirements in Sections 803.3.1 and
803.3.2 shall apply to occupancies in Group E.
803.3.1 Storage in corridors and lobbies. Clothing and
personal effects shall not be stored in corridors and lobbies.
Exceptions:
1. Corridors protected by an approved automatic
sprinkler system installed in accordance with Section
903.3.1.1.
2. Corridors protected by an approved smoke detection
system installed in accordance with Section
907.
3. Storage in metal lockers provided the minimum required
egress width is maintained.
803.3.2 Artwork. Artwork and teaching materials shall be
limited on the walls of corridors to not more than 20 percent
of the wall area.
803.4 Group I-4, day care facilities. The requirements in Sections
803.4.1 and 803.4.2 shall apply to day care facilities classified
in Group I-4.
803.4.1 Storage in corridors and lobbies. Clothing and
personal effects shall not be stored in corridors and lobbies.
Exceptions:
1. Corridors protected by an approved automatic
sprinkler system installed in accordance with Section
903.3.1.1.
2. Corridors protected by an approved smoke detection
system installed in accordance with Section
907.
3. Storage in metal lockers provided the minimum required
egress width is maintained.
803.4.2 Artwork. Artwork and teaching materials shall be
limited on walls of corridors to not more than 20 percent of
the wall area.

5). Fire alarm test report shall be submitted and all repairs shall be completed. IFC 901.6
6). Repair detector in laundry room. IFC 901.6
7). Unable to enter door in corridor. This must be entered to complete inspection.