Case: T07FR00415

Parcel: 14041059A


Addresses:

3265 E UNIVERSAL WY

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
10/12/2007 VIOL - MEANS OF EGRESS Approved -All OK.
03/06/2007 VIOL - MEANS OF EGRESS Violation 1.-Exit signs not working.
-Santa Rita room
-Main entrance
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.2003 IFC
***Repair/Replace Exit signs.
03/06/2007 VIOL - MEANS OF EGRESS Violation 2.-Exit lighting inoperable in emergency backup mode.
-Student breakroom, south wall.
-Chiricahua room.
-Student entrance hallway, west wall.
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate area.2003 IFC
***Repair/Replace Emergency illumination.