Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | VIOL - MEANS OF EGRESS | Approved | -All OK. | |
| 03/06/2007 | VIOL - MEANS OF EGRESS | Violation | 1.-Exit signs not working. -Santa Rita room -Main entrance 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.2003 IFC ***Repair/Replace Exit signs. |
|
| 03/06/2007 | VIOL - MEANS OF EGRESS | Violation | 2.-Exit lighting inoperable in emergency backup mode. -Student breakroom, south wall. -Chiricahua room. -Student entrance hallway, west wall. 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate area.2003 IFC ***Repair/Replace Emergency illumination. |