Case: T07FR00413

Parcel: 14041075A


Addresses:

3260 E UNIVERSAL WY

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
04/19/2007 VIOL - MEANS OF EGRESS Approved
03/06/2007 VIOL - MEANS OF EGRESS Violation 3.-Exit sign out of service. (Bldg. 1 north east corner)
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.2003 IFC
**Repair/replace exit sign.
03/06/2007 VIOL - MEANS OF EGRESS Violation 4.-Emergency illumination out of service. (Shipping/Receiving)
-South wall
-East wall
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate area.2003 IFC
**Repair/replace Emergency illumination.