Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 03/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 1.-Fire Department Connections (FDC) need signage to indicate location. 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “FDC” at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official.2003 IFC **install sign on covered parking eave to indicate FDC location. |
|
| 03/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 2.-Fire Extinguishers due for testing. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.2003 IFC **Schedule Extinguisher test. |