Case: T07FR00383

Parcel: 138240850

Inspection Status: Approved

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
03/07/2007 INSP - AST/UST Approved passed final inspection
03/01/2007 INSP - AST/UST Continued Inspection cancelled. spill protection not installed. Reinspection of the permanant spill protection will be next week.
02/23/2007 INSP - AST/UST Correction Required 1. need specs on tank to verify overfill protection
2. emergency shut-off needed between 20-100'
3. 5 gallon spill containment at fill site
4. break away on dispenser hose