Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - ADMINISTRATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | VIOL - ADMINISTRATION | Continued | IFC 105.6.17- This is pending the appeal to be signed by the fire code official. | |
| 03/14/2007 | VIOL - ADMINISTRATION | Approved | IFC 110.1- The 500 gallon tank has been triple rinsed by Southwest Fuel Care on 3/13/07. | |
| 02/21/2007 | VIOL - ADMINISTRATION | Violation | IFC 105.6.17- An operational permit is required to store, handle or use Class II & III liquids in excess of 60 gallons outside a building. A permit shall be obtained from both the Tucson Fire Dept and the Development Services Dept at 201 N Stone. | |
| 02/21/2007 | VIOL - ADMINISTRATION | Violation | IFC 110.1- Unsafe Conditions. Equipment that constitutes a fire hazard or is otherwise dangerous to human life or public welfare shall be deemed unsafe. The 500 gallon tank shall be pumped empty and shall be purged prior to removal. This tank is a non-listed, non-compliant tank and shall be removed from service. The 1000 gallon tank shall remain out of service until an acceptable alternative is approved by the fire marshal. The dispenser shall be secured against tampering. |