Case: T07FR00365

Parcel: 11108313D


Addresses:

2550 N DODGE BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR00365

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2007 INSP - FULL Approved
02/21/2007 INSP - FULL Violation 1). Currently many sprinkler head deflector are bent, these (but limited to) are the types of sprinkler heads that shall be replaced. IFC 901.6
2). Fire sprinkler test and inspection report shall be submitted and all repairs shall be completed. IFC 901.6
3). Fire alarm shall be maintained. Pull stations shall be maintained. NO changes shall be made to system with approval form Deputy Chief Dan Uthe, he can be reached at the address on form. IFC 901.6
4). Fire alarm system shall be tested and report submitted and all repairs completed. IFC 901.6
5). Exit signs shall be replaced or repaired. IFC 1026.3
6). Exit in dining room shall be unobstructed. IFC 1027.3
7). Repair all holes in B maintenance shop.