Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
07/17/2007 VIOL - FLAMMABLE LIQUIDS Approved all violations have been corrected.
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3404.2.6 Separation from incompatible materials. Storage of flammable and combustible liquids shall be separated from incompatible materials in accordance with Section 2703.9.8.
· Currently there are oxidizers stored next to flammables and combustibles in the Magnesium storage room.
- Separates oxidizers from incompatible materials
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3405.3.6.2.5 Separation. Multiple machines shall be separated from each other by a distance of not less than 30 feet (9144mm)or by a fire barrier with a minimum 1-hour fire-resistance rating.
· Provide the required separation between parts cleaning machines in the Accessory
Parts Cleaning Area
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3405.3.6.2.6 Ventilation. Machines shall be located in areas adequately ventilated to prevent accumulation of vapors.
· Provide adequate ventilation in all areas where parts cleaning machines are used
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3405.3.6.2.7 Installation. Machines shall be installed in accordance with their listings.
· Provide 6 feet separation between a parts cleaning machine and an unclassified power source or
· Adhere to the electrical specifications set forth in the manufacturer's instructions for installation. (GFCI outlet)
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3404.3.5 Storage in control areas. Storage of flammable and combustible liquids in control areas shall be in accordance with Sections 3404.3.5.1 through 3404.3.5.4.
· Currently the control areas are not clearly identified:
- Ensure control areas have not exceeded their maximum allowable quantities.
02/28/2007 VIOL - FLAMMABLE LIQUIDS Violation 3404.3.3.5.3 Orderly storage. Shelf storage of flammable and combustible liquids shall be maintained in an orderly manner.
· Currently there are 16 gallons of gasoline in containers stored in the Automotive Storage Room.
· Provide proper storage for all flammable liquids