Case: T07FR00361

Parcel: 124170410


Addresses:

805 S PARK AV

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE FINISHES

Date Description Inspector Results Comments
07/24/2007 VIOL - FLAMMABLE FINISHES Approved Sprinkler installed and approved by CShultz.
02/28/2007 VIOL - FLAMMABLE FINISHES Violation 1504.6 Fire protection. Spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system complying with Chapter 9 which shall also protect exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used.
ยท Provide automatic sprinkler coverage in accordance with chapter 15