Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2007 | VIOL - MEANS OF EGRESS | Not ready for Inspection | Required exits can not be determined until the building official does a final. All required exits must have a lit exit sign. This has been referred to the building inspector. | |
| 07/17/2007 | VIOL - MEANS OF EGRESS | Approved | Furnishings and decorations have been moved. The exits are no longer blocked. | |
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm) high on a contrasting background. · Place the approved sign above the main entrance doors on the West side of the building. |
|
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. · Remove all flush bolts on Door # 19 on SE corner of the building · Remove all flush bolts on Door # 17 on East side of the building · Remove flush bolts on Door # 7 on North side of the building |
|
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1027.4 Furnishings and decorations. Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. · Remove shelves obstructing - Door # 22 on West side of building - Door # 18 on West side of building |
|
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. · Illuminate, in an approved manner, all exits required by the Building Official |
|
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical. · Provide back up power supply for all required exit illumination |
|
| 02/28/2007 | VIOL - MEANS OF EGRESS | Violation | 1011.1/ 1011.2 Where required/ Illumination. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. · Illuminate, in an approved manner, all exit signs required by the Building Official |