Inspection History Details
Inspection Status: Revision
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | VIOL - FIRE PROTECTION SYSTEMS | Revision | Due to fire door placement, the square footage of the areas has been reduced below 12000 and sprinkler coverage is not required as a result of area. | |
| 02/28/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. · Inspect and maintain fire extinguisher in front lobby |
|
| 02/28/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. · Extinguisher in Joshua's work area must be mounted on an approved hanger or bracket. |
|
| 02/28/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 903.2.3 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exist: 1. Where a Group F-1 fire area exceeds 12,000 square feet (1115 m²); · Currently the square footage of your building exceeds 12,000 square feet. - Provide automatic sprinkler coverage in accordance with chapter 9. |