Case: T07FR00361

Parcel: 124170410


Addresses:

805 S PARK AV

Inspection Status: Revision

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
07/17/2007 VIOL - FIRE PROTECTION SYSTEMS Revision Due to fire door placement, the square footage of the areas has been reduced below 12000 and sprinkler coverage is not required as a result of area.
02/28/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
· Inspect and maintain fire extinguisher in front lobby
02/28/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied.
· Extinguisher in Joshua's work area must be mounted on an approved hanger or bracket.
02/28/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 903.2.3 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exist:
1. Where a Group F-1 fire area exceeds 12,000 square feet (1115 m²);
· Currently the square footage of your building exceeds 12,000 square feet.
- Provide automatic sprinkler coverage in accordance with chapter 9.