Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T07FR00361

Parcel: 124170410


Addresses:

805 S PARK AV

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/17/2007 VIOL - BUILDING SVCS & SYSTEMS Approved All violations have been corrected.
02/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
· Front Lobby ( West Wall).
· Balancing Room
· NW corner of Commercial Assembly Room
· Above ceiling in the Fuel Flow Area
· Flexible cords shall not extend through the wall in Welding Room.
02/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.4 Multiplug adapters. Multi-plug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
· Remove all unapproved multi-plug adapters:
- Behind the Reception Desk
- Machine Shop
- Balancing Room
- Test Cell: North wall
02/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
· Repair open wiring: Exterior East wall near the tank
· Chilean Parts room (2 ea.)
· Repair the light switch in Automotive Storage Area
· Repair the J-box in the Automotive Storage Area
· Over the exit in the Glass Bead Cleaning Room
· In the closet in the Glass Bead Room
· Place a blank in the electrical box in:
- The Fuel Parts storage area
- Balancing Room
· Replace outlet cover-plates:
- Hector's office (2 each)
- Light switch on the West wall in the fuel flow
- On the South wall near the floor in the fuel flow area
02/28/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used:
· Do not use unapproved/damaged cord on the fan in the Glass Bead Cleaning Room
· Outdoor Lighting near roof line shall be in accordance with the ICC Electrical Code
· Wiring on the electrical panel near door 17 shall be repaired (Currently the wiring is outside it's molding)
· Electrical wiring in the Control Room shall be in accordance with the ICC Electrical Code
· Other building electrical modifications and alterations shall be in accordance with the ICC electrical Code