Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T07FR00358

Parcel: 13824182B


Addresses:

1630 W COMMERCE CT

Inspection Status: Not ready for Inspection

Inspection History: VIOL - FIRE RESIST.RATED CONST

Date Description Inspector Results Comments
03/13/2007 VIOL - FIRE RESIST.RATED CONST Not ready for Inspection 1. Not finished, will call w/in 2 wks. when job is done.
02/27/2007 VIOL - FIRE RESIST.RATED CONST Violation 1. Holes in Drywall, Due to remodeling.( Q.C. room )
703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason shall
be protected with approved methods capable of resisting the
passage of smoke and fire.2003 IFC
***repair wall to preserve fire resistive construction.