Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T07FR00357

Parcel: 13216635A


Addresses:

3975 S EVANS BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
05/22/2008 VIOL - MEANS OF EGRESS Approved all o.k.
03/16/2007 VIOL - MEANS OF EGRESS Violation -Exit signs out of service.
(UPS pickup door)
(Receiving door)
1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose. 2003 IFC
***Repair to working order.
03/16/2007 VIOL - MEANS OF EGRESS Violation -Emergency lighting out of service.
(Mens' bathroom)
(Womens' bathroom)
(Receiving door)
(Q.C. lab)
(Shipping area [3])
1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the area. 2003 IFC
***Repair to working order.