Case: T07FR00355

Parcel: 136320080

Inspection Status: Continued

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00355

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Continued

Date Description Inspector Results Comments
04/13/2007 VIOL - FIRE PROTECTION SYSTEMS Continued
02/20/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 17. IFC 903.2.10 All new Group R Occ. except Groups R-3
An automatic sprinkler system shall be installed in the locations
set forth in Sections 903.2.10.1 through 903.2.10.1.3.
THE ENCLOSED GARAGE, NOW USED AS PART OF THE THE LIVING AREA, (ART ROOM), MUST BE SPRINKLERED. THIS MAY INCLUDE THE STORAGE CLOSETS ON THE EAST SIDE OF THE ROOM
1. THE SPRINKLER SYSTEM MUST BE EXTENED INTO THE ART ROOM.