Case: T07FR00348

Parcel: 116190140


Addresses:

430 N MAIN AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/27/2007 INSP - FULL Approved
02/16/2007 INSP - FULL Violation 1. Currently there is storage of combustible material in basement. Upon further research IFC 315.2.4 would apply:
315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood
core not less than 1.75 inches (44.5 mm) in thickness.
Storage shall not be placed on exposed joists.
Exceptions:
1. Areas protected by approved automatic sprinkler
systems.
2. Group R-3 and Group U occupancies.

2). Reattach heat detector shell -Basement IFC 901.6
3). Move combustible material 5 feet from hot water heater. IFC 315
4). Certificate of Occupancy required. IBC 110