Case: T07FR00341

Parcel: 12513002B


Addresses:

3242 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/13/2007 VIOL - FIRE PROTECTION SYSTEMS Approved
02/15/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 904.6.1 HOOD SYSTEMS SHALL BE INSPECTED AND TESTED FOR PROPER OPERATION AT 6 MOS. INTERVAL.
1) NEED YOUR HOOD SYSTEM TESTED AND DOCUMENTED.
02/15/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 2003 IFC 901.6 FIRE EXT. SHALL BE SERVICED ANNUALLY.
1) EXT. NEXT TO COFFE MACHINE.
2) EXT. NEXT TO MICROWAVE.
3) EXT. NEXT TO BACK DOOR IN KITCHEN.
02/15/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 2003 IFC 605.3.1 DOOR TO ELECTRICAL ROOM NEEDS TO BE MARKED WITH A SIGN STATING "ELECTRICAL ROOM"
02/15/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 2003 IFC 605.3 CLEAN AREA AROUND ELECTRICAL PANEL KEEPING ITEMS AWAY 30 INCHES WIDE BY 36 INCHES DEEP