Case: T07FR00307

Parcel: 140290640

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/23/2007 INSP - FULL Approved Final inspection.
02/09/2007 INSP - FULL Violation 2003 IFC-703.1 Ceiling tile missing. Fire resistance -rated construction shall be maintained. ( stock room).
2003 IFC-605.5 Extension cord in offices and throughout the business shall be removed or replaced with the power surge protectors.
2003 IFC-901.6 Fire sprinkler extinguisher system shall be serviced annually and shall have a current service tag attached.
2003 IFC-1011.2 Exit sign removed at this west exit door , shall repair install illuminated exit light.illuminated signs shall be in good working condtion at all times.
2003 IFC-A sprinkler head is needed in the wood storage shed.
2003 IFC-605.5 Warehouse need to remove extension cords.