Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00304
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 1. Panels clear. 2. Extension cords removed. 3. Switch blanks installed. |
|
02/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 1. Blocked electrical panels. 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space. TFC2003 ***Unblock Electrical Panels. |
|
02/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2. Extension Cords in use to power permanent equipment in Imaging, Pre-press rooms. 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. TFC2003 ***Remove extension cords and replace with UL/FM approved power strips. |
|
02/09/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 3. Electrical panel missing switch covers. 4. Blank outlet cover needed on missing outlet. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.TFC2003 ***Install switch cover plates in all missing locations in electrical panels. |