Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR00303
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | INSP - FULL | Approved | approved | |
| 02/09/2007 | INSP - FULL | Violation | 1). Certificate of occupancy shall be obtained. IBC 110 2). Fire alarm test and inspection report shall be submitted with smoke alarms and heat detectors addressed. All repairs shall be completed. IFC 901.6 3). All obstructions to exit discharge (side gates) shall be removed at once. IFC 1003.6 4). Exit lights are out of service in adult room shall be repaired. IFC 1026.3 5). Repair dry wall in electrical room IFC 703.1 6). Remove combustible material from electrical room IFC 315.2.3 7). Kitchen operations may require a hood extinguishing system. This shall be referred to DNR. |