Case: T07FR00303

Parcel: 113061320


Addresses:

3255 N CAMPBELL AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR00303

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2007 INSP - FULL Approved approved
02/09/2007 INSP - FULL Violation 1). Certificate of occupancy shall be obtained. IBC 110
2). Fire alarm test and inspection report shall be submitted with smoke alarms and heat detectors addressed. All repairs shall be completed. IFC 901.6
3). All obstructions to exit discharge (side gates) shall be removed at once. IFC 1003.6
4). Exit lights are out of service in adult room shall be repaired. IFC 1026.3
5). Repair dry wall in electrical room IFC 703.1
6). Remove combustible material from electrical room IFC 315.2.3
7). Kitchen operations may require a hood extinguishing system. This shall be referred to DNR.