Case: T07FR00300

Parcel: 11446020E

Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T07FR00300

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2007 INSP - AST/UST Approved passed inal inspection.
02/21/2007 INSP - AST/UST Continued Secondary piping inspection passed. Helium testing identified a leak in diesel line approximately 6 feet from canopy.
02/16/2007 INSP - AST/UST Denied Secondary piping inspection failed. Leak is between canopy and tanks (diesel). They will be performing helium test to find leak in existing piping.
02/15/2007 INSP - AST/UST Continued Primary piping passed.
02/07/2007 INSP - AST/UST Continued Site visit, contractor not on premises. Excavation has been started, new trench for E-stop added.