Case: T07FR00296

Parcel: 133251840


Addresses:

8530 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
02/23/2007 VIOL - PRECAUTION AGAINST FIRE Approved Guard posts installed. approved
02/15/2007 VIOL - PRECAUTION AGAINST FIRE Correction Required 312.2 Posts. Guard posts shall comply with all of the following
requirements:
1. Constructed of steel not less than 4 inches (102 mm) in
diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on
center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing
of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm)
above ground.
5. Located not less than 3 feet (914 mm) from the protected
object.
- Replace the 4 north bollards protecting the tank.