Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2007 | INSP - FULL | Approved | All violations complete no further action needed. | |
| 02/08/2007 | INSP - FULL | Correction Required | sprinkler connections, see above comments | |
| 02/08/2007 | INSP - FULL | Violation | 2003 IFC-503.1.1 Building approved fire apparatus access road is blooked by a six foot chain link fence.A 20 foot long gate can be installed with a knox box key for the fire department. This would make it accessable form the east and west. 2003 IFC-912.3 Acess. Immeddiate acess to fire department connections shall be maintainred at all times and with out obstruction by fence, bushes, trees, walls, or any other object for a mimimum of 3 feet. |