Case: T07FR00294

Parcel: 14108521C

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/28/2007 INSP - FULL Approved All violations complete no further action needed.
02/08/2007 INSP - FULL Correction Required sprinkler connections, see above comments
02/08/2007 INSP - FULL Violation 2003 IFC-503.1.1 Building approved fire apparatus access road is blooked by a six foot chain link fence.A 20 foot long gate can be installed with a knox box key for the fire department. This would make it accessable form the east and west.
2003 IFC-912.3 Acess. Immeddiate acess to fire department connections shall be maintainred at all times and with out obstruction by fence, bushes, trees, walls, or any other object for a mimimum of 3 feet.