Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T07FR00267
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | VIOL - FLAMMABLE LIQUIDS | Violation | 4. Group F occupancies: Quantities in dining, office, and school uses within Group F occupancies shall not exceed that necessary for demonstration, laboratory work, maintenance purposes and operation of equipment, and shall not exceed quantities set forth in Table 2703.1.1(1). All other flammable/ combustible liquids on site will not exceed 10 gallons in an open use system or 30 gallons accumulative in storage or use. All amounts above 30 gallons must be stored in a flammable liquids storage cabinet in a control area. No more than four control areas are allowed on your property. | |
02/07/2007 | VIOL - FLAMMABLE LIQUIDS | Violation | 3404.3.3.5.3 Orderly storage. Shelf storage of flammable and combustible liquids shall be maintained in an orderly manner. Arrange all Flammable and Combustible liquids in one control area for the facility. | |
02/07/2007 | VIOL - FLAMMABLE LIQUIDS | Violation | 3404.3.4.4 Liquids for maintenance and operation of equipment. In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 3404.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet when in approved containers located in private garages or other approved locations. All liquids stored in excess of 10 gallons and used to fuel equipment or will be placed in an approved and labled flammable liquids storage cabinet. |