Case: T07FR00232

Parcel: 12908025B


Addresses:

1601 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/14/2007 INSP - FULL Approved Final inspection.
01/31/2007 INSP - FULL Violation 2003 IFC-1008.1.8.4 Front exit door shall have the sign: This door to remain unlocked when building is occupied.
2003 IFC-605 Extension cords shall not be a substitute for permanent wiring.
2003 IFC-703.1 Ceiling tile missing a panel shall replace to keep the fire resistive construction. This is to prevent fire spead.
2003 IFC-304.3 Housekeeping in the shops, paper & oily rags.
2003 IFC-304 Flammable liquid gas can shell be in a flammable liquid cabinet.
2003 IFC-1003.3.6 Back exit door in the north shop is blocked.
2003 IFC-315 A self-closing metal can for the oily rags. The two shops shall have one can.