Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2007 | INSP - FULL | Approved | APPROVED | |
| 01/31/2007 | INSP - FULL | Violation | 1). Repair manual activation of kitchen hood extinguishing system. IFC 901.6 2). Kitchen hood extinguishing system is now due for 6 month servicing. IFC 904.11.6.2 3). 2nd floor exit sign shall be repaired. IFC 1026.3 4). 2nd floor egress light shall be repaired.. 1026. 5 5). Test smoke detectors and submit report. IFC 901.6 6). Replace panic hardware in enclosed stairwell. IFC 1008.1.1 7). Clean all mechanical rooms including sprinkler riser room and basement hot water heaters. IFC 315.2.3 |