Case: T07FR00229

Parcel: 130020350

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/07/2007 INSP - FULL Approved ALL ITEMS ABATED
01/30/2007 INSP - FULL Violation 1). Currently there is a window, in which is part of the playground boundaries (wall). This window is broken with broken glass shards exposed to all children in playground area. This shall be repaired immediately. This is an extreme safety hazard. IFC 110.1
Reinspection 1-31-07.

2). On the playground is a junked vehicle with many sharp and dangerous parts exposed to the children. This part of the playground shall be secured by 1-31-07 (and) car removed by 2-14-07
IFC 110.1

3). No address is posted. Address shall be posted as per Pima County premises display requirements standards. IFC 505.1

4). 3-Exit signs shall be repaired. IFC 1026.3

5). Repair hole in exterior of building. IFC 110.1