Inspection Status: Correction Required
Inspection History: INSP - REINSPECTION
| Date |
Description |
Inspector |
Results |
Comments |
| 02/21/2007 |
INSP - REINSPECTION |
|
Correction Required |
The vent lines that were installed are PVC and shall be replaced with steel pipe. The short vent on the west tank shall be capped. |
| 02/15/2007 |
INSP - REINSPECTION |
|
Correction Required |
Vent lines have been installed. They will need flame arrestors that are normally closed. |