Case: T07FR00196

Parcel: 11301146Z


Addresses:

1797 E PRINCE RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR00196

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
01/26/2007 VIOL - BUILDING SVCS & SYSTEMS Violation 3-2.8 Guards and Shields. Sprinklers subject to mechanical injury shall be protected with listed guards.
THE SPRINKLER HEAD IN THE WALK IN FREEZER SHALL HAVE A PROTECTIVE BASKET AROUND THE HEAD.
01/26/2007 VIOL - BUILDING SVCS & SYSTEMS Approved 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
1). ELECTRICAL CORD ON TRAEBAC MACHINE NEEDS TO BE REPAIRED/REPLACED.
2). ELECTRICAL CORD ON WELBILT MACHINE NEEDS TO BE SECURED TO WALL INSTEAD OF WRAPPING AROUND THE METAL RACK.
3). CEILING LIGHT IN OFFICE NEEDS TO BE SECURED TO CEILING.
01/26/2007 VIOL - BUILDING SVCS & SYSTEMS Approved 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor cover-
ings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
1). THE EXTENSION CORD IN THE DISPLAY CASE CANNOT BE USED AS PERMANENT WIRING.
2). THE ELECTRICAL CORD COMING THROUGH THE CEILING TILE SUPPLYING POWER TO THE PASTRY MACHINE CANNOT BE USED AS PERMANENT WIRING.
shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.
1). ELECTRICAL PLATE IS MISSING IN STORAGE ROOM ACROSS FROM OFFICE.
2). ELECTRICAL PLATE IS MISSING ON WEST WALL BY MIXING MACHINES.
REPLACE THE MISSING ELECTRICAL PLATES.