Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00196
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
01/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 3-2.8 Guards and Shields. Sprinklers subject to mechanical injury shall be protected with listed guards. THE SPRINKLER HEAD IN THE WALK IN FREEZER SHALL HAVE A PROTECTIVE BASKET AROUND THE HEAD. |
|
01/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. 1). ELECTRICAL CORD ON TRAEBAC MACHINE NEEDS TO BE REPAIRED/REPLACED. 2). ELECTRICAL CORD ON WELBILT MACHINE NEEDS TO BE SECURED TO WALL INSTEAD OF WRAPPING AROUND THE METAL RACK. 3). CEILING LIGHT IN OFFICE NEEDS TO BE SECURED TO CEILING. |
|
01/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cover- ings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 1). THE EXTENSION CORD IN THE DISPLAY CASE CANNOT BE USED AS PERMANENT WIRING. 2). THE ELECTRICAL CORD COMING THROUGH THE CEILING TILE SUPPLYING POWER TO THE PASTRY MACHINE CANNOT BE USED AS PERMANENT WIRING. shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1). ELECTRICAL PLATE IS MISSING IN STORAGE ROOM ACROSS FROM OFFICE. 2). ELECTRICAL PLATE IS MISSING ON WEST WALL BY MIXING MACHINES. REPLACE THE MISSING ELECTRICAL PLATES. |