Case: T07FR00196

Parcel: 11301146Z


Addresses:

1797 E PRINCE RD


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T07FR00196

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2007 VIOL - PRECAUTION AGAINST FIRE Approved
01/26/2007 VIOL - PRECAUTION AGAINST FIRE Violation 315.2.1 Ceiling clearance. Storage shall be maintained 18 inches
(or more below sprinkler head deflectors in sprinklered areas of buildings.)
1.)ALL STORAGE OF ITEMS SHALL BE MAINTAINED AT LEAST 18 INCHES FROM SPRINKLER HEADS.
2.)THE WALK-IN COOLER AND WALK-IN FREEZER SHALL HAVE ALL STORAGE ITEMS WHICH ARE CURRENTLY STORED ON TOP, TO BE REMOVED.
01/26/2007 VIOL - PRECAUTION AGAINST FIRE Violation 304.1 Waste accumulation prohibited. Combustible waste
material creating a fire hazard shall not be allowed to accumulate
in buildings or structures or upon premises.
CLEAN FLOURESENCE LIGHT FIXTURES WHICH HAVE A BUILD UP OF ACCUMULATION OF FLOUR WHICH CAN BE A SOURCE OF COMBUSTION. SET UP A MAINTENACE SCHEDULE, i.e. 6 MONTH OR ANNUAL, WHICH WILL HELP YOU MAINTAIN A SAFE WORKING ENVIRONMENT.

3-2.8 Guards and Shields. Sprinklers subject to mechanical injury shall be protected with listed guards.
THE SPRINKLER HEAD IN THE WALK IN FREEZER SHALL HAVE A PROTECTIVE BASKET AROUND THE HEAD.
01/26/2007 VIOL - PRECAUTION AGAINST FIRE Violation 308.5.2 Portable fueled open-flame devices. Portable
open-flame devices fueled by flammable or combustible
gases or liquids shall be enclosed or installed in such a manner
as to prevent the flame from contacting combustible material.
WHEN USING THE PORTABLE 2 BURNER PROPANE STOVE IT SHALL BE PLACED ON A STEEL TABLE TOP WITH A THREE (3) SIDED 8 INCH TALL METAL SHIELD FOR PROTECTION AGAINST COMBUSTIBLES.