Case: T07FR00186

Parcel: 12801020C


Addresses:

120 S WILMOT RD

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/20/2007 VIOL - MEANS OF EGRESS Approved corrected
01/24/2007 VIOL - MEANS OF EGRESS Correction Required 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.
- Maintain back up power source on all exit signs
01/24/2007 VIOL - MEANS OF EGRESS Correction Required 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.
- Maintain back up power supply for all emergency lights.