Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/20/2007 VIOL - FIRE PROTECTION SYSTEMS Approved corrected
01/24/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 912.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (914 mm).
- Provide a clear path to the sprinkler riser
01/24/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
- Replace escutcheon in the bistro side station.
- Repair escutcheons in the bar area.
- Provide an annual sprinkler test report.
01/24/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
- Provide a semi-annual kitchen hood test.
- Replace damaged or missing sprinkler nozzle covers.
- Clean or replace all clogged nozzles