Case: T07FR00140

Parcel: 12908007B


Addresses:

1625 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/30/2007 INSP - FULL Approved Final inspection.
04/25/2007 INSP - FULL Violation Almost complete, need more time on the electrical.
01/17/2007 INSP - FULL Violation 2003 IFC-Address shall be posted.
2003 IFC-1008.1.8.4 Need a exit sign at the front door.
2003 IFC-605.6 Open junction box over the office.
2003 IFC-105.3 Cof O shall be posted.
2003 IFC-3404.2.3.1 No smoking signs in the shops shall be posted.
2003 IFC-901.6 Fire extinguishers shall be seviced.
2003 IFC-2211.2.3 In the shope a self- closing metal.
2003 IFC-605.8 Flammables shall be stored orderly manner.
2003 IFC-3403.5 Label the 55-gals. to its product.
2003 IFC-315.2 Housekeeping throughout the shops.
2003 IFC-1003.3.6 Obstruction exit in the shop area.
2003 IFC-1504. Automatic sprinkler system shall be serviced annually.
2003 IFC-1504.6.1 Booth #1 & #2 protect the sprinkler heads with plastic baggies.
2003 IFC-1404.3.2.5 Exhaust intake needs the air filters.
2003 IFC-1504.1.2.5 A three foot clear space shall be provided.
2003 IFC-27003.4 MSDS sheets shall be posted.
2003 IFC-605.6 Booth #2 has a switch outside needs repair.
2003 IFC-901 Fire extinguisher behind cabinet relocate.
2003 IFC-605.6 Most of the eletrical in this araea needs repaired.
2003 IFC-Compress gas cylinder shall be secured.
2003 IFC-Housekeeping in body shop.
2003 IFC-No smoking sign shall be posted.
2003 iFC- The water supply line to the sprinklers shall be secured to prevent shut off.