Case: T07FR00121

Parcel: 133231400


Addresses:

7805 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00121

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/16/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 - ...egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove padlock and hardware from door leading from dining room to play area.

_____ Remove padlock and hardware from door leading from play area to public way.
01/16/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.5 - The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:
1. Group A having more than 50 occupants.

_____ Repair/replace emergency light, dining room west wall.