Case: T07FR00121

Parcel: 133231400


Addresses:

7805 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____ Mount electrical box at salsa bar.

_____ Close/repair panel door labled "Fryer Hood Fan" in electrical room.
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 - Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____ Cover wires in an approved manner, under dessert cooler

_____ Cover wires in an approved manner, electric box, freezer.

_____ Cover wires in an approved manner, switchplate cover outside office.
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____ Remove multi-plug adaptor (or replace with one having circuit protection), above drive-through monitor.

_____ Remove multi-plug adaptor (or replace with one having circuit protection), kitchen west wall near cooler.
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.2 - Illumination shall be provided for service equipment areas, motor control centers and electrical panelboards.

_____ Replace bulb in electrical room.
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3.1 - Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording.

_____ Provide such signage for electrical room doors outside back of building.