Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR00082
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2007 | INSP - FULL | Approved | approved | |
| 01/11/2007 | INSP - FULL | Violation | 1). Many doors leading to exit corridors are being left open. This is in violation of IFC 703.2.2 and IFC 703.2.3, which state: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position. All doors leading to corridors shall remain closed unless provided with a approved fire protection device. 2). Exit blocked by door 1136. IFC 1027.3 3). 2 sets of Doors closures shall be re installed on flammable liquid cabinets in Micolab. IFC 3404.3.2.1.3 4). Place exit sign at door 3132. IFC 1026.3 5). Exit sign out of service. Pima heart IFC 1026.3 6). Exit illumination light is out of service in Pima heart. IFC and Suite 201. IFC 1026.5 7). Label Sprinkler zone shut off on 4th floor SW Corner. IFC 903 8). Test results needed FIRE PUMP and FIRE ALARM test are to be submitted. IFC 901.6 9). New hood system in commercial cooking operations shall be installed by approved date of 3-1-07. 904.11 10). Door 408. Replace wood with proper rated material. IFC 703.1 11). Repair electrical in post morgue area. IFC 605.1 12. Please complete fire sprinkler deficiencies noted on annual test. Copy of test enclosed. IFC 901.6 |