Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR00082

Parcel: 11615088L

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR00082

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2007 INSP - FULL Approved approved
01/11/2007 INSP - FULL Violation 1). Many doors leading to exit corridors are being left open. This is in violation of IFC 703.2.2 and IFC 703.2.3, which state:

703.2.2 Hold-open devices and closers. Hold-open devices
and automatic door closers, where provided, shall be
maintained. During the period that such device is out of service
for repairs, the door it operates shall remain in the
closed position.
703.2.3 Door operation. Swinging fire doors shall close
from the full-open position and latch automatically. The
door closer shall exert enough force to close and latch the
door from any partially open position.

All doors leading to corridors shall remain closed unless provided with a approved fire protection device.

2). Exit blocked by door 1136. IFC 1027.3

3). 2 sets of Doors closures shall be re installed on flammable liquid cabinets in Micolab. IFC 3404.3.2.1.3

4). Place exit sign at door 3132. IFC 1026.3

5). Exit sign out of service. Pima heart IFC 1026.3

6). Exit illumination light is out of service in Pima heart. IFC and Suite 201. IFC 1026.5

7). Label Sprinkler zone shut off on 4th floor SW Corner. IFC 903
8). Test results needed FIRE PUMP and FIRE ALARM test are to be submitted. IFC 901.6

9). New hood system in commercial cooking operations shall be installed by approved date of 3-1-07. 904.11

10). Door 408. Replace wood with proper rated material. IFC 703.1

11). Repair electrical in post morgue area. IFC 605.1

12. Please complete fire sprinkler deficiencies noted on annual test. Copy of test enclosed. IFC 901.6