Case: T07FR00057

Parcel: 13419042D


Addresses:

7160 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00057

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2007 VIOL - MEANS OF EGRESS Approved corrected
01/09/2007 VIOL - MEANS OF EGRESS Correction Required 1016.2 Corridor width. The minimum corridor width shall be as determined in Section 1005.1, but not less than 44 inches (1118 mm).
-Maintain exit corridor width
01/09/2007 VIOL - MEANS OF EGRESS Correction Required 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. The emergency power system shall provide power for duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with
Section 604.
-Exit sign in the stock room shall have back up power