Case: T07FR00056

Parcel: 128100560


Addresses:

310 S WILLIAMS BL


Inspection Status: Compliance

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00056

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
06/12/2007 VIOL - FIRE PROTECTION SYSTEMS Compliance All violations have been corrected.
01/10/2007 VIOL - FIRE PROTECTION SYSTEMS Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed
with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. The required system must be extended as necessary to provide coverage under the drainage bins located in the basement Phone Circuit Board Room and in the West Elevator Equipment room. Contact the company who services, maintains and inspects your sprinkler system.