Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR00056
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | Compliance | All violations have been corrected. | |
01/10/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. The required system must be extended as necessary to provide coverage under the drainage bins located in the basement Phone Circuit Board Room and in the West Elevator Equipment room. Contact the company who services, maintains and inspects your sprinkler system. |